Leyon FM UL ESFR UPRIGHT SPRINKLER SIN VK520 K14.0

Fast response fusible sprinklers designed for early fire extinguishing. VK520 ESFR upright sprinklers can be used to protect common types of storage. They are primarily used to protect palletized and solid stacked storage, as well as single-row, double-row, multi-row and portable open rack storage.

Category

描述

Model VK520
Material Brass
Orientation Upright
K-factor, gpm/psi ½ (lpm/bar ½ ) 14.0 (202)
Maximum Working Pressure 175 psi (12 bar)
Temperature Rating °F (°C)1 165°F (74°C)-205°F (96°C)
Thread Size 3/4″ NPT (20 mm )